| Plan Review Notes For Permit 17080132 |
| Permit Number |
17080132 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-10-31 08:07:25 | PLAN | | | REVIEW COMMENTS | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) (PREVIOUS COMMENT) THE PLANS ARE REQUIRED TO HAVE | | | THE FLORIDA ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE, | | | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. CHAPTER | | | 471, FLORIDA STATUTES & 61G15-23.003 FLORIDA | | | ADMINISTRATIVE CODE | | | | | | 2) THE PERMIT APPLICATIONS FOR THE POOL AND POOL | | | PLUMBING ARE NOT WITH THE PERMIT DOCUMENTS. THE POOL | | | ELECTRICAL PERMIT (MISSING FROM THE FIRST REVIEW) IS | | | THE ONLY ONE THAT IS WITH THE DOCUMENTS. FBC 105.1 | | | | | | |
|