2017-09-15 17:01:381ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 REVISION #17080118
 MASTER PERMIT #15111020
 THE BRISTOL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CLOSET DOORS UO5G & UO5K MUST BE
 NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON
 THE MASTER SHEET A8.12 INDICATES WOOD DOORS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 COOKING APPLIANCE IN THE KITCHEN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL
 GAS.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2.
  
 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE
 PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT
 ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED-
 SECTION 601.5 (3).
  
 5) THE ELIMINATION OF BEDROOM #2 AND THE SUPPLY DUCT TO
 IT HAS REDUCED THE REQUIRED AIRFLOW FOR HP-F DOWN TO
 APPROXIMATELY 1250 CFMS, THEREFORE HP-F WHICH IS A 4.0
 TON UNIT PRODUCING 1700 CFMS APPEARS TO BE OVERSIZED
 FOR THE AREA IT IS SEVING.
  
 6) SHEETS M.54A & M54.B THAT ARE LISTED IN THE
 NARRATIVE WERE NOT UPLOADED FOR REVIEW.
  
 7) PROVIDE SUBDUCT INSTALLATION DETAILS.
  