| 2017-09-15 17:01:38 | 1ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE |
| | FBC. |
| | REVISION #17080118 |
| | MASTER PERMIT #15111020 |
| | THE BRISTOL |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC CLOSET DOORS UO5G & UO5K MUST BE |
| | NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON |
| | THE MASTER SHEET A8.12 INDICATES WOOD DOORS. |
| | |
| | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE |
| | COOKING APPLIANCE IN THE KITCHEN AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND |
| | SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL |
| | GAS. |
| | |
| | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE |
| | EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND |
| | SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2. |
| | |
| | 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE |
| | PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT |
| | ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED- |
| | SECTION 601.5 (3). |
| | |
| | 5) THE ELIMINATION OF BEDROOM #2 AND THE SUPPLY DUCT TO |
| | IT HAS REDUCED THE REQUIRED AIRFLOW FOR HP-F DOWN TO |
| | APPROXIMATELY 1250 CFMS, THEREFORE HP-F WHICH IS A 4.0 |
| | TON UNIT PRODUCING 1700 CFMS APPEARS TO BE OVERSIZED |
| | FOR THE AREA IT IS SEVING. |
| | |
| | 6) SHEETS M.54A & M54.B THAT ARE LISTED IN THE |
| | NARRATIVE WERE NOT UPLOADED FOR REVIEW. |
| | |
| | 7) PROVIDE SUBDUCT INSTALLATION DETAILS. |
| | |