| Plan Review Notes For Permit 17080108 |
| Permit Number |
17080108 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-15 16:30:23 | 1ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE | | | FBC. | | | REVISION #17080108 | | | MASTER PERMIT #15111020 | | | THE BRISTOL | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC CLOSET DOORS UO5K, UO5Q, MUST BE | | | NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON | | | THE MASTER SHEET A8.12 INDICATES WOOD DOORS. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE | | | COOKING APPLIANCE IN THE KITCHEN, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND | | | SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL | | | GAS. | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE | | | EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND | | | SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2. | | | | | | 4) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE | | | PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT | | | ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED- | | | SECTION 601.5 (3). | | | | | | 5) SHEETS M.54A & M54.B THAT ARE LISTED IN THE | | | NARRATIVE WERE NOT UPLOADED FOR REVIEW. | | | | | | 6) PROVIDE SUBDUCT INSTALLATION DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|