| Plan Review Notes For Permit 17080096 |
| Permit Number |
17080096 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-14 09:29:42 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE EXTERIOR DOOR PRODUCT APPROVAL THAT WAS | | | SUBMITTED (FL10537-R2) IS NOT THE ONE THAT IS SPECIFIED | | | ON THE PLANS (FL15227-R2). PLEASE CLARIFY. FBC | | | 107.3.4.1 | | | | | | 2) THE REQUIRED COMPONENT AND CLADDING PRESSURES FOR | | | THE NEW EXTERIOR DOORS ARE NOT SPECIFIED ON THE PLANS. | | | FBC-R301.2.1 | | | | | | 3) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE | | | REQUIRED FROM ROOMS USED FOR SLEEPING. THIS IS AN | | | EXISTING SINGLE FAMILY DWELLING AND FBC EXISTING | | | BUILDING SECTION 704.1 HAS AN EXECPTION THAT ALLOWS A | | | MAXIMUM 5 PERCENT REDUCTION IN THE CLEAR OPENING | | | DIMENSIONS OF REPLACEMENT WINDOWS AS LONG AS THE | | | PORTION OF THE BUILDING IS NOT ALTERED SUCH THAT THE | | | BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITION | | | PER SECTION 701.2. SHOW ON THE PLANS HOW THE NEW | | | WINDOWS WILL COMPLY WITH SECTION 701.2 OR HOW THE | | | OPENINGS WILL BE ALTERED TO COMPLY WITH FBC-R310.1. |
|