| Date |
Text |
| 2017-11-07 14:40:58 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR WILL |
| | BRING REQUIRED INFORMATION PRIOR TO INSPECTIONS TO |
| | AVOID CONFLICTS/DELAYS. REVISION FEES APPLY. |
| | CONTRACTOR TO ADVICE IN WRITING IF PROVISO OPTION IS |
| | PREFERRED AT THIS TIME. |
| | |
| | |
| | |
| | 1- A/C PLAN NEEDS TO SHOW COMPLIANCE WITH THE BALANCED |
| | RETURN AIR FOR ALL ROOMS REQUIRED BY SEC. M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: |
| | A) SIZE OF TRANSFER DUCT SPECIFIED FOR THE MASTER |
| | BEDROOM IS TOO SMALL. SIZE NEEDS TO BE BE BASED ON THE |
| | TOTAL SUPPLY AIR THAT GOES INTO THE MASTER BEDROOM, |
| | INCLUDING THE CLOSETS AND BATHROOM. SEE EXCEPTION #3 OF |
| | SEC. M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 19" DUCT |
| | SIZE (BASED ON THE SPECIFIED CFM'S) AND HAVING THE DOOR |
| | WITH AT LEAST AN UNRESTRICTED 1 INCH UNDERCUT. REVISE |
| | AS REQUIRED. REPEAT COMMENT. REVISED SIZE OF 14" |
| | DOESN'T COMPLY. NEED AT LEAST 19" DUCT. |
| | |
| | B) SIZE OF TRANSFER DUCT SPECIFIED FOR THE |
| | STUDY/BEDROOM AND BEDROOMS #2 AND #3 IS TOO SMALL. THE |
| | SIZE OF THE DUCT NEEDS TO BE 1-1/2 TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM AND HAVING THE DOOR WITH AT LEAST AN |
| | UNRESTRICTED 1 INCH UNDERCUT. SEE EXCEPTION #1 OF SEC. |
| | M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 10" DUCT SIZE. |
| | REVISE AS REQUIRED. REPEAT COMMENT. SIZE WAS NOT |
| | REVISED. NEED AT LEAST 10" DUCT. |
| | |
| | C) EQUIPMENT SIZING CALCULATIONS SHOW A 4 TON A/C UNIT. |
| | CFM'S SHOWN ON THE A/C PLAN EXCEED THE CAPACITY OF THE |
| | EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING |
| | CALCULATIONS. REVISE CFM'S AS REQUIRED. SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: COORDINATE INFORMATION WITH PLANS SUBMITTED WITH |
| | THE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | D) MECHANICAL PLAN M-101 IS MISSING THE CFM'S FOR THE |
| | DINING ROOM. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: |
| | WHEN THE AIR HANDLING UNIT IS LOCATED IN THE ATTIC, THE |
| | SERVICE PANEL NEED TO BE WITHIN 6 FEET OF THE ATTIC |
| | ACCESS AS REQUIRED BY SEC. R403.2.4 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS... |
| | *****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SET. |
| | SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION. |
| | (561)805-6712 |
| | [email protected] |