| Plan Review Notes For Permit 17080065 |
| Permit Number |
17080065 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 10:33:54 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13. | | | | | | USE FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE | | | CALCULATIONS. | | | | | | 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS | | | RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF | | | SYSTEM WORKING PRESSURE. | | | 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE | | | PRESSURE OR VISUAL LEAKAGE. | | | | | | | | | 3.3.19 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED | | | STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO | | | SPRINKLER SYSTEM COMPONENTS EXCLUSIVE OF SURGE | | | PRESSURES AND EXCLUSIVE OF PRESSURE FROM THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|