| 2017-08-21 10:45:05 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW CLEAR FLOOR SPACE TO COMPLY WITH FBC ACC |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 2. KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 CLEAR |
| | FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. A BACKFLOW IS REQUIRED ON REFRIGERATOR ICE MACHINE. |
| | PER FBC PL 608.3 |
| | |
| | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |