Plan Review Notes
Plan Review Notes For Permit 17080055
Permit Number 17080055
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-15 07:46:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080055
 8/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: THE CITY OF WEST PALM BEACH BUILIDNG DIVISION
 REQUIRES A DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM
 OF THE 5-TON SYSTEM UNLESS MANUFACTURER'S
 SPECIFICATIONS INDICATE THE SYSTEM CANNOT PRODUCE
 SUPPLY AIR IN EXCESS OF 2000 CFMS- SECTION 606.2.1.
  
 2) M-1: LABEL THE O/A DUCT.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA USED IN
 DESIGNING THE ACCU TIE-DOWN DETAIL- SECTION 301.15.
  
 4) THE BUILDING PLANS EXAMINER IS INDICATING THAT THE
 PROPOSED PROJECT IS A CHANGE OF OCCUPANCY. PLEASE SEE
 SECTION C101.4.4 FBC-14 ENERGY CONSERVATION. PLEASE
 NOTE THAT SUBMUITTED ENERGY FORM C402-2014 CAN NOT BE
 USED FOR A CHANGE OFPOCCUPANCY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  