| 2017-08-15 07:46:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17080055 | | | 8/15/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: THE CITY OF WEST PALM BEACH BUILIDNG DIVISION | | | REQUIRES A DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM | | | OF THE 5-TON SYSTEM UNLESS MANUFACTURER'S | | | SPECIFICATIONS INDICATE THE SYSTEM CANNOT PRODUCE | | | SUPPLY AIR IN EXCESS OF 2000 CFMS- SECTION 606.2.1. | | | | | | 2) M-1: LABEL THE O/A DUCT. | | | | | | 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA USED IN | | | DESIGNING THE ACCU TIE-DOWN DETAIL- SECTION 301.15. | | | | | | 4) THE BUILDING PLANS EXAMINER IS INDICATING THAT THE | | | PROPOSED PROJECT IS A CHANGE OF OCCUPANCY. PLEASE SEE | | | SECTION C101.4.4 FBC-14 ENERGY CONSERVATION. PLEASE | | | NOTE THAT SUBMUITTED ENERGY FORM C402-2014 CAN NOT BE | | | USED FOR A CHANGE OFPOCCUPANCY COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|