Plan Review Notes
Plan Review Notes For Permit 17080055
Permit Number 17080055
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-09 07:34:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC C405.5
 2. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. SOME AREAS DO NOT SHOW EITHER A
 TIMER CONTROLLOED CIRCUIT OR OCCUPANCY SENSORS
 REQUIRED. FBC C405.2.2, 405.2.2.2
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC C405.7.1
 4. WILL THERE BE ANY SHOW WINDOWS IN THIS BUSINESS?
 PROVIDE SHOW WINDOW LIGHTING OUTLETS IF NECESSARY. NEC
 210.62
 5. PROVIDE AUTOMATIC CONTROL FOR SIGN LIGHTING.
 "LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS'. FBC
 C405.2.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  