| Plan Review Notes For Permit 17080055 |
| Permit Number |
17080055 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 13:09:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY (FROM | | | BUSINESS TO MERCANTILE); REVISE PLAN TO INCLUDE THIS | | | INFORMATION. SEE FBC EB CHAPTER 10 AND REVISE PLAN TO | | | SHOW COMPLIANCE WITH ALL REQUIREMENTS. IF THIS SPACE | | | WAS BUSINESS, MERCANTILE IS A HIGHER HAZARD. | | | | | | 2. CONFERENCE ROOMS SHOULD HAVE AN OCCUPANT LOAD | | | UTILIZING 15 SF PER PERSON, FBC B 1004, REVISE. | | | | | | |
|