Plan Review Notes
Plan Review Notes For Permit 17080045
Permit Number 17080045
Review Stop B
Sequence Number 2
Notes
Date Text
2017-10-17 17:55:00***PROVISOS***
  
 1. THRESHOLD BUILDING - THREE SETS OF PLANS REQUIRED.
 AFTER ISSUANCE, HAVE A FULL SIZE COPY OF THE PLANS MADE
 FOR THE SPECIAL INSPECTOR.
  
 2. 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT OR ENGINEER IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC.
  
 4. COORDINATE WITH BUILDING INSPECTOR: WITH THE
 EXTERIOR STAIRS, RAMP (WEST SIDE OF THE BUILDING) AND
 THE ENTRY DOORS ON BOTH THE WEST AND EAST SIDES BEING
 REPLACED, PLEASE PROVIDE AN EGRESS PLAN OF HOW EGRESS
 WILL BE MAINTAINED DURING CONSTRUCTION.
  
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS TO ANY BUILDING.
 EXCEPTION: EXISTING MEANS OF EGRESS NEED NOT BE
 MAINTAINED WHERE APPROVED TEMPORARY MEANS OF EGRESS
 SYSTEMS AND FACILITIES ARE PROVIDED.
  
 5. SEPARATE PERMITS REQUIRED FOR IRRIGATION, FIRE
 ALARM, FIRE SPRINKLER, LOW VOLTAGE.
  