2017-08-15 10:46:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 022 - THUIS SHEET INDICATES THE REMOVAL OF
 TWO SETS OF DOUBLE DOOR AT EACH END OF THE BRIDGE.
 SHEET A 202, INDICATES THE REINSTALLATION OF ONLY ONE
 SET.
  
 THE CONCERN LIES WITH WHAT WAS THE ORIGINAL LIFE SAFETY
 INTENT OF THESE DOORS AND WOULD REMOVING ONE SET
 COMPROMISE THE LIFE SAFETY FEATURES ORIGNALLY DESIGNED.
  
 PLEASE REVIEW THE EOR AND ENSURE THAT THESE DOORS DO
 NOT NEGATIVELY AFFECT THE LIFE SAFETY FEATURES OF THE
 BUILDING.
  
 PER NFPA 101
  
 8.6.7* ATRIUMS. UNLESS PROHIBITED BY CHAPTERS 11
 THROUGH 43, AN ATRIUM SHALL BE PERMITTED, PROVIDED THAT
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY
 FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING, WITH OPENING PROTECTIVES FOR
 CORRIDOR WALLS, UNLESS ONE OF THE FOLLOWING IS MET:
 (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO
 EXISTING, PREVIOUSLY APPROVED ATRIUMS.
 (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE
 PERMITTED TO OPEN DIRECTLY TO THE ATRIUM WITHOUT
 ENCLOSURE, BASED ON THE RESULTS OF THE ENGINEERING
 ANALYSIS REQUIRED IN 8.6.7(5).
 (C)* GLASS WALLS AND INOPERABLE WINDOWS SHALL BE
 PERMITTED IN LIEU OF THE FIRE BARRIERS WHERE ALL THE
 FOLLOWING ARE MET:
 I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES OF
 THE GLASS WALL AND THE INOPERABLE WINDOWS AT INTERVALS
 NOT TO EXCEED 6 FT (1830 MM).
 II. THE AUTOMATIC SPRINKLERS SPECIFIED IN
 8.6.7(1)(C)(I) ARE LOCATED AT A DISTANCE FROM THE GLASS
 WALL NOT TO EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT
 THE ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION
 OF THE SPRINKLERS.
 III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED
 GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS THE
 GLASS FRAMING SYSTEM TO DEFLECT WITHOUT BREAKING
 (LOADING) THE GLASS BEFORE THE SPRINKLERS OPERATE.
 IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(1)(C)(I)
 ARE NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL
 AND THE INOPERABLE WINDOW WHERE THERE IS NO WALKWAY OR
 OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE THE MAIN
 FLOOR LEVEL.
 V. DOORS IN THE GLASS WALLS ARE OF GLASS OR OTHER
 MATERIAL THAT RESISTS THE PASSAGE OF SMOKE.
 VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON DETECTION OF SMOKE.
 VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT
 HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER
 OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING OF
 THE ENTIRE GLASS SURFACE.
 (2) ACCESS TO EXITS IS PERMITTED TO BE WITHIN THE
 ATRIUM, AND EXIT DISCHARGE IN ACCORDANCE WITH 7.7.2 IS
 PERMITTED TO BE WITHIN THE ATRIUM.
 (3) THE OCCUPANCY WITHIN THE ATRIUM MEETS THE
 SPECIFICATIONS FOR CLASSIFICATION AS LOW OR ORDINARY
 HAZARD CONTENTS. (SEE 6.2.2.)
 (4) THE ENTIRE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
 (5)* FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED
 ATRIUMS, AN ENGINEERING ANALYSIS IS PERFORMED THAT
 DEMONSTRATES THAT THE BUILDING IS DESIGNED TO KEEP THE
 SMOKE LAYER INTERFACE ABOVE THE HIGHEST UNPROTECTED
 OPENING TO ADJOINING SPACES, OR 6 FT (1830 MM) ABOVE
 THE HIGHEST FLOOR LEVEL OF EXIT ACCESS OPEN TO THE
 ATRIUM, FOR A PERIOD EQUAL TO 1.5 TIMES THE CALCULATED
 EGRESS TIME OR 20 MINUTES, WHICHEVER IS GREATER.
 (6)* IN OTHER THAN EXISTING, PREVIOUSLY APPROVED
 ATRIUMS, WHERE AN ENGINEERED SMOKE CONTROL SYSTEM IS
 INSTALLED TO MEET THE REQUIREMENTS OF 8.6.7(5), THE
 SYSTEM IS INDEPENDENTLY ACTIVATED BY EACH OF THE
 FOLLOWING:
 (A) REQUIRED AUTOMATIC SPRINKLER SYSTEM
 (B) MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE
 FIRE DEPARTMENT
  
 PROVIDE APPLICABLE DETAILS/PLAN SHEETS/EOR DOCUMENTS,
 ETC
  
  
  
 2) SHEET A 500 - THE DOOR SCHEDULE INDICATES NO RATING
 FOR DOOR B002.
  
 PLEASE REVIEW WITH # 1 ABOVE TO ENSURE THAT THIS DOOR
 IS NOT REQUIRED TO CARRY ANY RATING.
  
 PROVIDE APPLICABLE DETAILS/PLAN SHEETS/EOR DOCUMENTS,
 ETC
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  