Plan Review Notes
Plan Review Notes For Permit 17080045
Permit Number 17080045
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-24 08:17:112014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080045
 ADD: 515 N. FLAGLER DR.
 CONT: GLENEWINKEL CONSTRUCTION CO.
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 23/ 2014
 ACTION: DENIED
  
 1)THRESHOLD BUILDING. THIS BUILDINGS STRUCTURAL
 ALTERATIONS BEING A HIGHRISE BUILDING MEETS THE
 QUALIFICATIONS FOR A SPECIAL INSPECTOR. FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2) SHEET A-021AT GRID LINE B1-B2/ 5.1-6.5 ALSO HAS A
 NOTE NUMBER D-4 REFERS TO THE REMOVAL OF STAIRS, REFERS
 AGAIN TO THE STRUCTURAL NARRATIVE FOR THE EXTENT OF
 REMOVAL. SHEET A-201 THE SAME PLAZA LEVEL MAKES NO
 REFERENCE TO A FLOOR INFILL. SHEET S-202 SHOWS A DETAIL
 AT THE REMOVED STAIR 09/ S-401. NO SUCH DETAIL ON SHEET
 S-401. WERE THE STAIRS THAT WERE REMOVED JUST
 CONVENIENCE STAIRS IT APPEARS THAT THERE WAS NO SHAFT?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3A) SHEET A-021 THE PLAZA DEMO HAS NOTE # 5 TO REMOVE
 THE EXISTING VESTIBULE, AND ENTRANCE DOORS AND
 SIDELIGHTS. SHEET A-201 SHOWS THE ENTRY DOORS IN A NEW
 LOCATION. SHEET A-600 HAS THE DOOR SCHEDULE AND THESE
 DOORS LISTED AS DOORS L002 A & B. THERE IS NO REFERENCE
 IF THESE DOORS ARE NEW ARE OR TRYING TO BE REUSED. SEE
 THE W. P. B. ADMINISTRATIVE CODE REFERENCE TO USED
 MATERIALS.
  
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED
 RECYCLED OR RECLAIMED MATERIALS WHICH MEET THE
 REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE
 REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL.
  
 NEW EXTERIOR DOORS WILL NEED TO COMPLY WITH COMPONENTS
 & CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
  
 3B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) SHEET A-201 INDICATES DETAIL G.1/ A-411 THIS DETAIL
 REFERS TO DETAIL A,15 OF THE SAME SHEET A-411. THIS
 DETAIL IS OF THE NEW VESTIBULE WALL PLAN.
  
 4A) WITHIN THIS DETAIL THE WALL PANELS SHOW THE USE OF
 STEEL STUDS, THE TYPE OF STEEL STUD, STRUCTURAL OR
 ARCHITECTURAL, GAUGE OF STUD, SPACING IS NOT PROVIDED.
 2014 FBC-B 2211.1 AND OR 2211.4 WALL STUD DESIGN.
  
 4B) SHEET A-411 DETAIL A,15 INDICATES THE USE AND
 INSTALLATION OF MCM PANELS (METAL COMPOSITE MATERIALS)
 PLEASE PROVIDE THE MANUFACTURERS REPORT PROVING
 COMPLIANCE WITH SECTIONS 1407.1- 1407.9.
  
 4C) NEW MCM PANELS WILL NEED TO COMPLY WITH COMPONENTS
 & CLADDING. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (C) PANEL WALLS: MCM PANELS AND PRODUCTS
 INTRODUCED AS A RESULT OF NEW TECHNOLOGY.
  
 5) WITH THE EXTERIOR STAIRS, RAMP (WEST SIDE OF THE
 BUILDING) AND THE ENTRY DOORS ON BOTH THE WEST AND EAST
 SIDES BEING REPLACED, PLEASE PROVIDE AN EGRESS PLAN OF
 HOW EGRESS WILL BE MAINTAINED DURING CONSTRUCTION.
  
 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS TO ANY BUILDING.
 EXCEPTION: EXISTING MEANS OF EGRESS NEED NOT BE
 MAINTAINED WHERE APPROVED TEMPORARY MEANS OF EGRESS
 SYSTEMS AND FACILITIES ARE PROVIDED.
  
 6) PLEASE REVIEW SHEET A-201 SEE STAIR SHAFT IN GRID
 LINES B3-B4 & 5.1-6. IN THE PAST THERE WAS CREATED A
 NONCONFORMITY IN THE STAIRWELL (SHAFT). IT APPEARS
 THERE WAS A DOOR REMOVED FROM THE PARKING LEVEL THAT
 LET DIRECT ACCESS INTO THE ATRIUM AREA. THE PLANS HAVE
 THIS BLOCKED OFF BUT THE PLANS DO NOT RATE THE WALL AS
 A 2 HOUR WALL. THE HIGHRISE STAIR ENCLOSURE IS A 2 HOUR
 FIRE RATED SHAFT. THIS PORTION OF THE WALL IS A INFILL,
 PLEASE REQUIRE A 2 HOUR FIRE RATED WALL IN THIS INFILL.
 2014 FBC-B 713.4.
  
 7) SHEET A-301 SHOWS NEW EXTERIOR GLASS GUARDRAIL
 SYSTEMS WITH LAMINATED STRUCTURAL GLASS WITH # 4
 STAINLESS CAP. PLEASE PROVIDE SHOP DRAWING TO BE
 REVIEWED BY THE DESIGNER OF RECORD BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. SHOW COMPLIANCE
 WITH 2014 FBC-B 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.8. A
 SAFETY FACTOR OF (4) FOUR SHALL BE USED.
  
 8) SHEET A540 DETAIL A,1 THE SOUTH ELEVATION. THIS
 ELEVATION SHOWS AN ALTERNATE GLAZING DETAIL FOR ? INCH
 CLEAR TEMPERED BUTT JOINT GLAZING. TWO ISSUES:
 8A) IS THIS GLAZING TO THE EXTERIOR? IF SO DOES THE
 BUTT JOINT TEMPERED GLAZING HAVE PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT TESTING? COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 8B) THE PLANS INDICATE THE BUTT JOINT GLAZING AS AN
 ALTERNATIVE, 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION."
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  