| Plan Review Notes For Permit 17080035 |
| Permit Number |
17080035 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 09:58:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE IS AN ENGINEERS REPORT FOR UPLIFT CALCULATIONS | | | FOR A 10' X 20' TENT. | | | | | | THE TIE DOWN SCHEDULE INDICATES A 20' X 20' TENT WITH | | | WEIGHTED 5 GALLON CEMENT BUCKETS AT EACH LEG. | | | | | | NO WHERE IN THE ENGINEER'S REPORT DOES IT INDICATE | | | ANYTHING ABOUT THE USE OF A 5 GALLON CEMANT BUCKETS AS | | | AN ALTERNATIVE OR EQUAL TO THE TIE DOWN REPORT. | | | | | | IT ALSO DOES NOT INDICATE TIE DOWN FOR 20' X 20' TENT. | | | | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|