2017-08-04 09:58:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN ENGINEERS REPORT FOR UPLIFT CALCULATIONS
 FOR A 10' X 20' TENT.
  
 THE TIE DOWN SCHEDULE INDICATES A 20' X 20' TENT WITH
 WEIGHTED 5 GALLON CEMENT BUCKETS AT EACH LEG.
  
 NO WHERE IN THE ENGINEER'S REPORT DOES IT INDICATE
 ANYTHING ABOUT THE USE OF A 5 GALLON CEMANT BUCKETS AS
 AN ALTERNATIVE OR EQUAL TO THE TIE DOWN REPORT.
  
 IT ALSO DOES NOT INDICATE TIE DOWN FOR 20' X 20' TENT.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  