2017-08-08 10:32:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080021
 8/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB CONSTRUCTION SERVICES RECORDS FOR THE MASTER AND
 SUB-PERMITS ON THE PROJECT DO NOT SHOW A VALUE FOR THE
 MECHANICAL SCIOPE OF WORK. PLEASE PROVIDE ON THE
 REVISION FORM THE INCREASED VALUE FOR THE AC CHANGE OUT
 AND DUCTWORK ASSOCIATED WITH THE PROJECT- SECTION 109.3
 WPB AMENDMENTS TO THE FBC.
  
 2) PLEASE CLARIFY THE SCOPE OF WORK FOR THE DUCTWORK-
 IS THIS A COMPLETE OR PARTIAL REPLACEMENT?
  
 3) SHOW THE SUPPLY CFMS AT EACH DIFFUSER, AND PROVIDE
 RETURN AIR FROM THE BEDROOMS- SECTION 601.5
  