| Plan Review Notes For Permit 17071275 |
| Permit Number |
17071275 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 09:44:24 | RESIDENTIAL (R3) ELEVATION CERTIFICATE BUILDING REVIEW | | | COMMENTS. | | | | | | 1- FINAL EQUIPMENT ELEVATION SHOWN ON PAGE 2 OF 6 | | | DOESN'T COMPLY WITH THE CITY CODE SEC. 94-546(B)(1). | | | BASED ON THE PERMIT APPLICATION, THE ELEVATION NEED TO | | | BE AT LEAST 6" ABOVE THE BASE FLOOD ELEVATION. THE BASE | | | FLOOD ELEVATION FOR FLOOD ZONE A5 IS 7'-0". THEREFORE, | | | EQUIPMENT NEEDS TO BE ELEVATED AND RE-INSPECTION IS | | | REQUIRED. | | | | | | 2- ITEM #C2(B) ON PAGE 2 OF 6 NEEDS TO BE COMPLETED. | | | THIS IS A TWO STORY RESIDENCE. NA IS INCORRECT. SEC. | | | 107.2.1 CITY AMENDMENTS. SEC. R322 FBC-RESIDENTIAL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|