2017-08-04 09:44:24RESIDENTIAL (R3) ELEVATION CERTIFICATE BUILDING REVIEW
 COMMENTS.
  
 1- FINAL EQUIPMENT ELEVATION SHOWN ON PAGE 2 OF 6
 DOESN'T COMPLY WITH THE CITY CODE SEC. 94-546(B)(1).
 BASED ON THE PERMIT APPLICATION, THE ELEVATION NEED TO
 BE AT LEAST 6" ABOVE THE BASE FLOOD ELEVATION. THE BASE
 FLOOD ELEVATION FOR FLOOD ZONE A5 IS 7'-0". THEREFORE,
 EQUIPMENT NEEDS TO BE ELEVATED AND RE-INSPECTION IS
 REQUIRED.
  
 2- ITEM #C2(B) ON PAGE 2 OF 6 NEEDS TO BE COMPLETED.
 THIS IS A TWO STORY RESIDENCE. NA IS INCORRECT. SEC.
 107.2.1 CITY AMENDMENTS. SEC. R322 FBC-RESIDENTIAL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  