| 2017-08-30 08:55:16 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #17071273 |
| | 8/30/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 2) BASED ON THE BUILDING PLAN REVIEW COMMENT #1 |
| | INDICATING THE PROPOSED PROJECT MAY BE A CHANGE OF |
| | OCCUPANCY, PLEASE REVIEW SECTION C101.4.6 FBC-14 ENERGY |
| | CONSERVATION AND PROVIDE A COMPLIANCE SUBMITTAL- SEE |
| | SECTION C401.2 FOR COMPLIANCE PATH INFORMATION. |
| | |
| | 3) SHEETS M1.1 & M1.2: PLEASE PROVIDE AC EQUIPMENT |
| | SCHEDULES LISTING THE MAKES AND MODELS OF THE EXISTING |
| | SYSTEMS, AND THE SYSTEM CAPACITIES- COOLING AND HEATING |
| | BTUHS AND TOTAL SUPPLY CFMS. |
| | |
| | 4) M1.1 & M1.2: SHOW THE RETURN AIR SYSTEMS. PLEASE |
| | NOTE THAT SMOKE DETECTORS MAY BE REQUIRED WHERE SYTEMS |
| | EXCEED 2000 CFMS IN CAPACITY- SECTION 606.2.1. |
| | |
| | 5) M1.1: PLAN NOTE #3 INDICATES FIRE DAMPERS AT DUCT |
| | PENETRATIONS HOWEVER NO DUCTS ARE SHOWN AT THESE |
| | LOCATIONS. IT APPEARS THAT THE THESE ARE TRANSFER |
| | GRILLS. PLEASE REVIEW SECTION 601.2 WHICH PROHIBITS AIR |
| | TO BE TRANSFERRED TO A CORRIDOR AS A MEANS OF RETURNING |
| | AIR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |