| Plan Review Notes For Permit 17071268 |
| Permit Number |
17071268 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-02 06:06:22 | 1) THE MODEL OF THE DEVICE YOU HAVE HIGHLITED ON THE | | | SPECIFICATIONS IS NOT LEAD FREE AS REQUIRED BY THE CITY | | | OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL AND | | | ONLY THE NON-LEAD FREE DEVICE IS NOTED ON THE | | | SPECIFICATION SHEET AS BEING ON THE USC LIST OF | | | APPROVED DEVICES. | | | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. | | | 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF | | | SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. | | | 4) AN IRRIGATION CONTRACTOR CANNOT INSTALL AN APPROVED | | | BACKFLOW DEVICE ON A POTABLE WATER LINE.SEE COPY OF | | | "STANDARDS FOR CERTIFIED CONTRACTORS" THAT I PLACED IN | | | THE PERMIT APPLICATION FILE FROM PALM BEACH COUNTY | | | CONTRACTOR LICENSING SECTION FOR SCOPE OF WORK FOR | | | IRRIGATION CONTRACTORS. THE BACKFLOW DEEVICE MUST BE | | | INSTALLED BY A LICENSED PLUMBING CONTRACTOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-805-6692 | | | [email protected] | | | |
|