Plan Review Notes
Plan Review Notes For Permit 17071262
Permit Number 17071262
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-08 11:43:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A CLEAR PLAN OF THE ELECTRICAL WORK BEING
 PERFORMED.
  
 SCETCH SHOWS WIRES RUNNING THRU METAL FRAMING MEMBERS
 THIS WOULD NOT BE ACCEPTABLE, NO GROUND WIRE SHOWN AND
 OPEN CONDUCTORS.
  
 SOME TYPE OF CABLE WOULD BE RQUIRED IN ORDER TO WIRE
 THIS ROOM.
  
 SHOW WHERE POWER COMES FROM AND HOW DC MOTORS GET THEIR
 POWER
  
 FAN TO BE LISTED FOR WET LOCATION NAD LIGHT FIXTURES IF
 USED....