| Plan Review Notes For Permit 17071245 |
| Permit Number |
17071245 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-03 16:10:30 | 1) PLEASE INDICATE THE MODEL OF THE PVB ON THE | | | SPECIFICATIONS ONE IS NOT LEAD FREE AS REQUIRED BY THE | | | CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL | | | AND ONLY THE NON-LEAD FREE DEVICE IS NOTED ON THE | | | SPECIFICATION SHEET AS BEING ON THE USC LIST OF | | | APPROVED DEVICES. | | | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. | | | 3) THE LEAD FREE MODEL OF THE PVB IS NOT LISTED ALL | | | BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. | | | 4) PLEASE INDICATE ON APPLICATION WHERE THESE DEVISES | | | WILL BE INSTALLED. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|