Plan Review Notes
Plan Review Notes For Permit 17071224
Permit Number 17071224
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-15 12:23:421ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17071224
 8/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1: THE BUILDING PRESSURIZATION TABLE IS
 INCORRECTLY INDICATING NEUTRAL PRESSURE, HOWEVER IT
 SHOULD READ -200. PLEASE CORRECT AND PROVIDE THE MAKE
 UP AIR FOR THE ROTARY OVEN IN THE CALCULATION TABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER