| Plan Review Notes For Permit 17071224 |
| Permit Number |
17071224 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-15 12:23:42 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17071224 | | | 8/15/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.1: THE BUILDING PRESSURIZATION TABLE IS | | | INCORRECTLY INDICATING NEUTRAL PRESSURE, HOWEVER IT | | | SHOULD READ -200. PLEASE CORRECT AND PROVIDE THE MAKE | | | UP AIR FOR THE ROTARY OVEN IN THE CALCULATION TABLE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|