2017-08-09 09:19:041ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17071224
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW 2.5 TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REVISE THE ENERGY COMPLIANCE FORM TO INCLUDE THE NEW
 AC SYSTEM.
  
 3) SHEET M0.1: PLEASE PROVIDE THE BUILDING
 PRESSURIZATION AND KITCHEN EXHAUST TABLES THAT ARE
 MISSING FROM THE REVISED PLAN SHEET.
  