| Plan Review Notes For Permit 17071224 |
| Permit Number |
17071224 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-09 09:19:04 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION PERMIT #17071224 | | | 8/9/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW 2.5 TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) REVISE THE ENERGY COMPLIANCE FORM TO INCLUDE THE NEW | | | AC SYSTEM. | | | | | | 3) SHEET M0.1: PLEASE PROVIDE THE BUILDING | | | PRESSURIZATION AND KITCHEN EXHAUST TABLES THAT ARE | | | MISSING FROM THE REVISED PLAN SHEET. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|