2017-08-09 14:43:441) PROVIDE A NARRATIVE AS TO HOW THE SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTOR WERE DONE. I DO
 NOT UNDERSTAND HOW YOU ARRIVED AT THESE NUMBERS AND
 CANNOT CONFIRM COMPLIANCE WITH THE PLUMBING CODE .
 CLARIFY.
 2) THE MINIMUM SLOPE ON A 2 INCH PIPE IS 1/4 INCH PER
 FOOT PER 2014 FPC TABLE 704.1.
  