| Plan Review Notes For Permit 17071132 |
| Permit Number |
17071132 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-09 14:43:44 | 1) PROVIDE A NARRATIVE AS TO HOW THE SIZING | | | CALCULATIONS FOR THE GREASE INTERCEPTOR WERE DONE. I DO | | | NOT UNDERSTAND HOW YOU ARRIVED AT THESE NUMBERS AND | | | CANNOT CONFIRM COMPLIANCE WITH THE PLUMBING CODE . | | | CLARIFY. | | | 2) THE MINIMUM SLOPE ON A 2 INCH PIPE IS 1/4 INCH PER | | | FOOT PER 2014 FPC TABLE 704.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|