| 2017-08-01 10:01:38 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE GREASE TRAP. 2014 FBC-PLUMBING | | | SEC.1003.2. | | | 2) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP. THE | | | TRAP MAY BE SIZED USING STANDARD PDI G101. 2014 | | | FBC-PLUMBING SEC.1003.3.4. | | | 3) THE INLET & OUTLET OF THE GREASE TRAP SHALL BE | | | INDIRECTLY WASTED PER 2014 FBC- PLUMBING SEC. 802.1.8. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|