| Plan Review Notes For Permit 17071125 |
| Permit Number |
17071125 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-27 06:21:54 | 1) SUBMIT DOCUMENTATION FROM THE PALM BEACH COUNTY | | | HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING | | | PERMIT HAS BEEN SUBMITTED TO THE HEALTH DEPARTMENT FOR | | | THIS SWIMMING POOL. FL. STATUTE 514.03 (1). | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL | | | HEAT PUMPS. THE HEAT PUMPS SHALL COMPLY WITH THE 2014 | | | FBC - ENERGY SEC.C404.7.1 AND TABLE C404.2. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN | | | DRAIN GRATES. THE MAXIMUM VELOCITY OF THE WATER PASSING | | | THROUGH THE OPENINGS SHALL NOT EXCEED 1 1/2 FEET PER | | | SECOND AT 100 PERCENT OF THE DESIGN RECIRCULATION | | | FLOW.. 2014 FBC SEC.454.1.6.5.10.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|