Plan Review Notes
Plan Review Notes For Permit 17071125
Permit Number 17071125
Review Stop P
Sequence Number 2
Notes
Date Text
2017-12-27 06:21:541) SUBMIT DOCUMENTATION FROM THE PALM BEACH COUNTY
 HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING
 PERMIT HAS BEEN SUBMITTED TO THE HEALTH DEPARTMENT FOR
 THIS SWIMMING POOL. FL. STATUTE 514.03 (1).
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEAT PUMPS. THE HEAT PUMPS SHALL COMPLY WITH THE 2014
 FBC - ENERGY SEC.C404.7.1 AND TABLE C404.2.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN GRATES. THE MAXIMUM VELOCITY OF THE WATER PASSING
 THROUGH THE OPENINGS SHALL NOT EXCEED 1 1/2 FEET PER
 SECOND AT 100 PERCENT OF THE DESIGN RECIRCULATION
 FLOW.. 2014 FBC SEC.454.1.6.5.10.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  