| 2017-09-14 14:23:19 | 1) SUBMIT DOCUMENTATION FROM THE PALM BEACH COUNTY |
| | HEALTH DEPARTMENT THAT AN APPLICATION FOR AN OPERATING |
| | PERMIT HAS BEEN SUBMITTED TO THE HEALTH DEPARTMENT FOR |
| | THIS SWIMMING POOL. FL. STATUTE 514.03 (1). |
| | 2) THE FILTRATION SYSTEM SHALL BE CAPABLE OF MEETING |
| | ALL OTHER REQUIREMENTS OF 2014 FBC-BUILDING, CHAPTER |
| | 454 WHILE ALSO PROVIDING A FLOW RATE OF AT LEAST 3/4 |
| | GPM FOR EACH LIVING UNIT AT NONTRANSIENTFACILITIES. |
| | 2014 FBC-BUILDING SEC.454.1.1.1. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| | HEAT PUMPS. THE HEAT PUMPS SHALL COMPLY WITH THE 2014 |
| | FBC - ENERGY SEC.C404.7.1 AND TABLE C404.2. |
| | 4) THE FLOOR INLETS SHALL NOT EXCEED 10 FEET FROM |
| | ADJACENT POOL WALLS AND SHALL NOT EXCEED 20 FEET |
| | BETWEEN ADJACENT FLOOR INLETS. 2014 FBC-BUILDING |
| | SEC.454.1.6.5.9.4. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| | DRAIN GRATES. THE MAXIMUM VELOCITY OF THE WATER PASSING |
| | THROUGH THE OPENINGS SHALL NOT EXCEED 1 1/2 FEET PER |
| | SECOND AT 100 PERCENT OF THE DESIGN RECIRCULATION |
| | FLOW.. 2014 FBC SEC.454.1.6.5.10.2. |
| | 6) THE FLOW RATE THROUGH EACH FLOOR INLET SHALL NOT |
| | EXCEED 20 GPM. 2014 FBC SEC.454.1.6.5.9.6. |
| | 7) SHT. 7 OF 7 - PIPING NOTES - #6 READS THAT THE POOL |
| | WATER SHALL DISCHARGE TO THE SANITARY SYSTEM. POOL |
| | WATER IS NOT PERMITTED TO DISCHARGE TO THE CITY'S |
| | SANITARY OR STORM PER CITY CODE OF ORDINANCES ART.III, |
| | SEC. 90-126 (SANITARY) AND ART.V, SEC.90-203 |
| | (STORMWATER). PLEASE CONTACT MANNY GONZALEZ WITH THE |
| | CITY OF WEST PALM BEACH ENGINEERING DEPT.AT |
| | 561-494-1085. |
| | 8) A MINIMUM OF A DOUBLE CHECK VALVE BACKFLOW PREVENTER |
| | SHALL BE INSTALLED ON THE POTABLE WATER SUPPLY FOR THE |
| | POOL PER THE CITY OF WPB CROSS CONNECTION MANUAL. |
| | 9) ALL CHEMICALS SHALL BE FED INTO THE RETURN LINE |
| | AFTER THE PUMP, HEATER AND FILTERS PER 2014 FBC SEC. |
| | 454.1.6.5.16. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |