| Plan Review Notes For Permit 17071121 |
| Permit Number |
17071121 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-31 11:29:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) FLEX DROPS ARE INDICATED ON THE PLAN SHEET. THERE IS | | | NO INDICATION OF HOW MANY FLEX DROPS OR WHERE THE FLEX | | | DROPS ARE LOCATED. NO FLEX DROP SPECS WERE PROVIDED. | | | | | | A REVIEW OF THE EOR HYDRALIC DOCUMENTS IS WARRANTED DUE | | | TO THE HIGHER FRICTION LOSS INHERENT OF FLEX DROPS. | | | | | | PLEASE PROVIDE A REVIEW OF THE HYDRALIC CALCULATIONS | | | THAT INCLUDES THE PROPOSED FLEX DROPS, HOW MANY, THE | | | PROPOSED LOCATIONS AND FLEX DROP SPEC SHEETS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|