| Plan Review Notes For Permit 17071106 |
| Permit Number |
17071106 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-04 10:49:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE COVER SHEET INDICATES "THIS BUILDING IS | | | NON-SPRINKLED CONDOMINIUM" AND IS INCORRECT. THE | | | BUILDING IS SPRINKLERED. THE FIRE SPRINKLER SYSTEM | | | SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | | | | 2) ANY WORK ON FIRE ALARM EQUIPMENT SHALL BE DONE UNDER | | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|