2017-12-20 14:15:07I HAVE REVIEWED THE RESPONSE LETTER DATED AUG. 10, 2017
 FROM MS. SHERRY BROWN OF GLOBAL SECURITY. THE LETTER
 INDICATES 3 REASONS WHY FIRE ALARM NOTIFICATION
 APPLIANCES ARE NEEDED; HOWEVER, NONE OF THE REASONS ARE
 SUPPORTED BY NFPA 72. IF THE FIRE INSPECTOR FIELD
 RESULTS INDICATE LOW AUDIBILITY IN THE NEW FREEZERS,
 THEN TO MEET THE AUDIOBILITY REQUIREMENTS OF NFPA 72,
 TYPICALLY FIRE ALARM NOTIFICATION DEVICES WILL BE
 REQUIRED IN THESE LARGE COOLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL