| 2017-12-20 14:15:07 | I HAVE REVIEWED THE RESPONSE LETTER DATED AUG. 10, 2017 | | | FROM MS. SHERRY BROWN OF GLOBAL SECURITY. THE LETTER | | | INDICATES 3 REASONS WHY FIRE ALARM NOTIFICATION | | | APPLIANCES ARE NEEDED; HOWEVER, NONE OF THE REASONS ARE | | | SUPPORTED BY NFPA 72. IF THE FIRE INSPECTOR FIELD | | | RESULTS INDICATE LOW AUDIBILITY IN THE NEW FREEZERS, | | | THEN TO MEET THE AUDIOBILITY REQUIREMENTS OF NFPA 72, | | | TYPICALLY FIRE ALARM NOTIFICATION DEVICES WILL BE | | | REQUIRED IN THESE LARGE COOLERS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | [email protected] |
|