| Plan Review Notes For Permit 17071087 |
| Permit Number |
17071087 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-01-05 12:13:27 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 4. DETAIL 1-S1.0 SPECS SELF DRILLING SCREWS PER | | | MANUFACTURER REQUIREMENTS. DETAIL 2-M2 ALSO REFERS TO | | | MANUFACTURER INSTRUCTIONS. FBC B 1609, REVISE DETAILS | | | TO SPECIFY FASTENING INCLUDING DIAMETER, LENGTH, | | | FASTENING PATTERN. IF THIS WILL BE DELEGATED | | | ENGINEERING PER FLORIDA ADMINISTRATIVE CODE 61G15-30, | | | PROVIDE THE DELEGATED ENGINEERING (UNIT FASTENING TO | | | CURB, ANY OTHER ) AT THIS TIME. STRUCTURAL ENGINEER OF | | | RECORD (SEOR) TO REVIEW DELEGATED ENGINEERING PRIOR TO | | | SUBMITTAL. | | | | | | DETAIL WAS NOT REVISED BUT A NEW NOTE REFERS TO THIS AS | | | "DELEGATED ENGINEERING". SUBJECT TO INSPECTOR'S | | | DISCRETION, A REVISION MAY BE REQUIRED. | | | | | | |
|