| 2017-08-09 08:45:44 | 1ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING, & |
| | ENERGY CONSERVATION CODES. |
| | PERMIT #17071087 |
| | 8/9/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET R3: REFER TO SECTION 1104.2 AND INDICATE THE |
| | AMOUNT OF REFRIGERANT IN EACH CIRCUIT. |
| | |
| | 2) REM2: CLARIFY IF EMERGENCY VENTILATION WILL BE |
| | PROVIDED AT LEAK DETECTION ALARM LOCATIONS. |
| | |
| | 3) PROVIDE REFRIGERANT PIPING SPECIFICATIONS- SECTION |
| | 1107.5. |
| | |
| | 4) PROVIDE SUBMITTALS FOR THE LEAK DETECTORS, PIPING |
| | INSULATION, AND PIPING PENETRATION SEALANTS. PLEASE |
| | NOTE THAT ALL SUBMITTALS SHALL BE APPROVED BY THE |
| | ENGINEER OF RECORD. |
| | |
| | 5) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR ALL |
| | NEW RTU'S- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 6) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR |
| | SYSTEMS OF ALL NEW AND REPLACED RTU'S- SECTION 606.2.1. |
| | PLEASE NOTE THIS REQUIREMENT WILL BE WAIVED IF |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS ARE |
| | NOT CAPABLE OF SUPPLYING OVER 2000 CFMS OF AIR. |
| | |
| | 7) REFER TO TABLE 403.3 AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL NEW ROOMS AND SPACES. |
| | |
| | 8) THE PLAN IS SPECIFYING "NEW" AND "REPLACED" RTU'S. |
| | PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENINGS |
| | AND SUPPORTS FOR THE NEW RTU'S. |
| | |
| | 9) M2: SUBMIT THE LENNOX BRACKET SPECIFICATIONS WITH |
| | APPROVAL STAMP BY THE ENGINEER OF RECORD. THE EOR SHALL |
| | SPECIFY HOW MANY BRAQCKETS AND SCREWS ARE REQUIRED PER |
| | WIND LOAD CALCULATIONS- SECTION 301.15. |
| | |