2017-08-09 08:45:441ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING, &
 ENERGY CONSERVATION CODES.
 PERMIT #17071087
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET R3: REFER TO SECTION 1104.2 AND INDICATE THE
 AMOUNT OF REFRIGERANT IN EACH CIRCUIT.
  
 2) REM2: CLARIFY IF EMERGENCY VENTILATION WILL BE
 PROVIDED AT LEAK DETECTION ALARM LOCATIONS.
  
 3) PROVIDE REFRIGERANT PIPING SPECIFICATIONS- SECTION
 1107.5.
  
 4) PROVIDE SUBMITTALS FOR THE LEAK DETECTORS, PIPING
 INSULATION, AND PIPING PENETRATION SEALANTS. PLEASE
 NOTE THAT ALL SUBMITTALS SHALL BE APPROVED BY THE
 ENGINEER OF RECORD.
  
 5) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR ALL
 NEW RTU'S- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 6) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN AIR
 SYSTEMS OF ALL NEW AND REPLACED RTU'S- SECTION 606.2.1.
 PLEASE NOTE THIS REQUIREMENT WILL BE WAIVED IF
 MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS ARE
 NOT CAPABLE OF SUPPLYING OVER 2000 CFMS OF AIR.
  
 7) REFER TO TABLE 403.3 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL NEW ROOMS AND SPACES.
  
 8) THE PLAN IS SPECIFYING "NEW" AND "REPLACED" RTU'S.
 PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENINGS
 AND SUPPORTS FOR THE NEW RTU'S.
  
 9) M2: SUBMIT THE LENNOX BRACKET SPECIFICATIONS WITH
 APPROVAL STAMP BY THE ENGINEER OF RECORD. THE EOR SHALL
 SPECIFY HOW MANY BRAQCKETS AND SCREWS ARE REQUIRED PER
 WIND LOAD CALCULATIONS- SECTION 301.15.
  