2017-08-01 10:04:41CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL SPECS FOR ALL NEW EQUIPMENT TO BE
 INSTALLED INCLUDING MINIMUM CIRCUIT AMPACITY
 REQUIREMENTS AND MAXIMUM OVERCURRENT PROTECTION
 REQUIRED PER MANUFACTURER. NEC 110.3; FBC 107.2.1
 2. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH BRANCH
 CIRCUIT TO ANY NEW EQUIPMENT INSTALLED. ALTHOUGH NOT
 SUPPLIED WITH THE AMPACITY REQUIREMENTS NOTED IN
 COMMENT #1, AN ESTIMATED VOLTAGE DROP CALCULATION SHOWS
 THAT SOME EXISTING WIRING APPEARS TO NOT BE SIZED
 ADEQUATELY TO COMPLY WITH FBC ENERGY CODE. PROVIDE
 CORRECTIONS AS NECESSARY SO THAT CONDUCTORS ARE SIZED
 FOR A MAXIMUM VOLTAGE DROP OF 3%. FBC C405.7.3.2, FBC
 107.2.1
 3. SHEET E1, RTU SCHEDULE, SHOWS A DIFFERENT VALUE FOR
 THE REQUIRED OCPD AND THE EXISTING OCPD. THE BRANCH
 CIRCUIT OVERCURRENT PROTECTION DEVICE RATING SHALL BE
 THE SIZE AND TYPE MARKED ON THE EQUIPMENT. NEC 110.3,
 440.22(C)
 4. SHEET RE3, CASE DEFROST DETAIL, STATES THAT B PHASE
 IS A HIGH LEG, BUT ALSO STATES THAT THIS IS A 208 VOLT
 SYSTEM WHICH DOES NOT HAVE A HIGH LEG. PLEASE CLARIFY
 AND/OR CORRECT. FBC 107.2.1
 5. PROVIDE PANEL SCHEDULE FOR ANY PANEL AFFECTED BY
 PROPOSED WORK. INCLUDE DETAILS OF WIRING AND BREAKER
 SIZE FOR NEW AND ALTERED CIRCUITS. INCLUDE TOTAL LOAD
 CALCULATED FOR PANEL TO CONFIRM THE CAPACITY OF PANEL
 IS SUFFICIENT TO SUPPLY LOADS. NEC 215.5, 408.4,
 408.30; FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  