| 2017-08-01 10:04:41 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL SPECS FOR ALL NEW EQUIPMENT TO BE |
| | INSTALLED INCLUDING MINIMUM CIRCUIT AMPACITY |
| | REQUIREMENTS AND MAXIMUM OVERCURRENT PROTECTION |
| | REQUIRED PER MANUFACTURER. NEC 110.3; FBC 107.2.1 |
| | 2. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH BRANCH |
| | CIRCUIT TO ANY NEW EQUIPMENT INSTALLED. ALTHOUGH NOT |
| | SUPPLIED WITH THE AMPACITY REQUIREMENTS NOTED IN |
| | COMMENT #1, AN ESTIMATED VOLTAGE DROP CALCULATION SHOWS |
| | THAT SOME EXISTING WIRING APPEARS TO NOT BE SIZED |
| | ADEQUATELY TO COMPLY WITH FBC ENERGY CODE. PROVIDE |
| | CORRECTIONS AS NECESSARY SO THAT CONDUCTORS ARE SIZED |
| | FOR A MAXIMUM VOLTAGE DROP OF 3%. FBC C405.7.3.2, FBC |
| | 107.2.1 |
| | 3. SHEET E1, RTU SCHEDULE, SHOWS A DIFFERENT VALUE FOR |
| | THE REQUIRED OCPD AND THE EXISTING OCPD. THE BRANCH |
| | CIRCUIT OVERCURRENT PROTECTION DEVICE RATING SHALL BE |
| | THE SIZE AND TYPE MARKED ON THE EQUIPMENT. NEC 110.3, |
| | 440.22(C) |
| | 4. SHEET RE3, CASE DEFROST DETAIL, STATES THAT B PHASE |
| | IS A HIGH LEG, BUT ALSO STATES THAT THIS IS A 208 VOLT |
| | SYSTEM WHICH DOES NOT HAVE A HIGH LEG. PLEASE CLARIFY |
| | AND/OR CORRECT. FBC 107.2.1 |
| | 5. PROVIDE PANEL SCHEDULE FOR ANY PANEL AFFECTED BY |
| | PROPOSED WORK. INCLUDE DETAILS OF WIRING AND BREAKER |
| | SIZE FOR NEW AND ALTERED CIRCUITS. INCLUDE TOTAL LOAD |
| | CALCULATED FOR PANEL TO CONFIRM THE CAPACITY OF PANEL |
| | IS SUFFICIENT TO SUPPLY LOADS. NEC 215.5, 408.4, |
| | 408.30; FBC 107.2.1, 107.3.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |