| Date |
Text |
| 2017-10-06 10:23:50 | HOLD ON PERMIT ISSUANCE UNTIL THE CITY IS IN RECEIPT OF |
| | JAMES BARRETT BN2612 RESUME'. |
| | |
| | ROOFING PRODUCT APPROVALS BEING RETURNED, REQUIRES |
| | SIGNED AND SEALED ENHANCED FASTENING BY ENGINEER, |
| | SUBMITTED NOT SIGNED AND SEALED. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17071073 |
| | W. P. B. PERMIT: 16071078 |
| | ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-662-8049 |
| | E-MAIL: [email protected] |
| | |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. OCT. 04/ 2017 |
| | ACTION: BUILDING PROVISO/ APPROVED WITH EXCEPTION |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THEIR PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEES. |
| | |
| | 1) SHEET A-102A |
| | 1A) REVISION REQUIRED. CAPTION DORMS REQUIRE 1 HOUR |
| | FIRE RATED WALLS, SEE WALL TAG (2) UL U-465. SHOWERS |
| | SHOW A WALL TAG (5) NOT FIRE RATED, DOES NOT GO ALL THE |
| | WAY TO THE DECK ABOVE. 2014 FBC-B 420.2 / 708.3. |
| | |
| | 1B) REVISION REQUIRED. COMMON WALL BETWEEN DORM (5) AND |
| | LAUNDRY WALL TAG (10), PLEASE REFER BACK TO WALL |
| | IDENTIFICATION TAG (2) AND UL LISTING U465 A 1 HOUR |
| | FIRE RATED WALL TYPE. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |