| 2017-08-10 11:13:44 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER SHOWS 1/0 WIRE USED FOR A 200 AMP SERVICE. 1/0 |
| | WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| | 215.2, 310.15; FBC RE3602.1 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. INCLUDE ALL AVAILABLE GROUNDING ELECTRODES. |
| | NEC 250.50, 250.94; FBC RE3609.3 |
| | 3. NOTE # 2 REFERENCES THE 2008 NEC FOR AFCI |
| | PROTECTION. 2008 NEC IS NOT CURRENT CODE. PROVIDE |
| | CORRECTION. FBC PREFACE |
| | 4. NOTE # 3 STATES ALL SLEEPING AREAS SHALL HAVE AFCI |
| | PROTECTION. THE CODE REQUIRES MORE THAN JUST SLEEPING |
| | AREAS TO HAVE AFCI PROTECTION. REVISE TO REFLECT CODE. |
| | NEC 210.12; FBC RE3902.12, FBC 107.2.1 |
| | 5. NOTE # 4 REFERENCES THE 2008 NEC, SECTION 406.11 FOR |
| | TAMPER RESISTANT OUTLETS. PROVIDE CORRECTION. NEC |
| | 406.12; FBC RE4002.14 |
| | 6. WATER HEATER BREAKER IS TOO LARGE. PROVIDE |
| | CORRECTION. NEC 422.13 |
| | 7. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS |
| | ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE, |
| | WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED |
| | FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC |
| | RE3705.4.4 |
| | 8. AHU UNIT APPEARS TO BE IN ATTIC. PROVIDE OUTLET AT |
| | OR NEAR THE APPLIANCE. FBC RESIDENTIAL M1305.1.3.1 |
| | 9. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF |
| | FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC |
| | RE4003.12 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |