| Plan Review Notes For Permit 17070927 |
| Permit Number |
17070927 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-27 10:45:49 | 1) THE BACKFLOW DEVICE SHALL BE LOCATED AT THE WATER | | | METER PER THE CITY OF WPB CROSS-CONNECTION MANUAL. 2ND | | | REQUEST.THE SUBMITTED DRAWING SHOWS THE DEVICE AT THE | | | FICUS TREES. CONTACT THE UTILITIES DEPT.AT | | | 561-822-2240. FOR APPROVAL OF THE BACKFLOW LOCATION. | | | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE | | | SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THE DEVICE IS | | | LEAD FREE. 2ND REQUEST. | | | 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF | | | SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. | | | 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO | | | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE | | | CITY'S REQUIREMENTS. | | | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS THAT SHOW THE DEVICE IS LEAD FREE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|