| Plan Review Notes For Permit 17070921 |
| Permit Number |
17070921 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-31 16:18:55 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FLORIDA PRODUCT APPROVAL SUBMITTED AND ENGINEER'S | | | CALCULATIONS SUBMITTED DON'T MATCH. FLORIDA PRODUCT | | | APPROVAL SUBMITTED IS FL2948-R10, ENGINEER IS | | | REFERENCING THE CURRENT REVISED FLORIDA PRODUCT | | | APPROVAL FL2948-R11. SUBMIT 2 COPIES OF THE CURRENT | | | FLORIDA PRODUCT APPROVAL FL2948-R11 THAT MATCHES | | | ENGINEER'S CALCULATIONS. | | | SEC. 107.2.1 CITY AMENDMENTS. FAC 61G20-3001. | | | | | | 2- ENGINEER'S CALCULATIONS SUBMITTED NEED TO HAVE THE | | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUE WHEN SUBMITTING DOCUMENTS | | | FOR PUBLIC RECORDS. PROVIDE TWO NEW CALCULATIONS WITH | | | ORIGINAL SEAL AND SIGNATURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|