Plan Review Notes
Plan Review Notes For Permit 17070921
Permit Number 17070921
Review Stop B
Sequence Number 2
Notes
Date Text
2017-07-31 16:18:55RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLORIDA PRODUCT APPROVAL SUBMITTED AND ENGINEER'S
 CALCULATIONS SUBMITTED DON'T MATCH. FLORIDA PRODUCT
 APPROVAL SUBMITTED IS FL2948-R10, ENGINEER IS
 REFERENCING THE CURRENT REVISED FLORIDA PRODUCT
 APPROVAL FL2948-R11. SUBMIT 2 COPIES OF THE CURRENT
 FLORIDA PRODUCT APPROVAL FL2948-R11 THAT MATCHES
 ENGINEER'S CALCULATIONS.
 SEC. 107.2.1 CITY AMENDMENTS. FAC 61G20-3001.
  
 2- ENGINEER'S CALCULATIONS SUBMITTED NEED TO HAVE THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS. PROVIDE TWO NEW CALCULATIONS WITH
 ORIGINAL SEAL AND SIGNATURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]