Plan Review Notes
Plan Review Notes For Permit 17070904
Permit Number 17070904
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-22 17:01:111ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 TOP OF GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. WATER-HAMMER ARRESTORS SHALL BE INSTALLED ON ICE
 MACHINES COFFEE MAKERS AND DISHWASHERS AND ANY SENSOR
 FAUCETS. PER FBC PL 604.9
  
 3. A BACKFLOW IS REQUIRED ON THE ICE MAKERS AND COFFEE
 MAKERS. PER FBC PL 608.3, 608.16.10
  
 4. TEMPERED WATER IS REQUIRED AT THE LAVATORY FAUCET.
 PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH