| Date |
Text |
| 2017-07-26 17:10:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET 002 - THERE ARE NO INDICATIONS OF REVIEW |
| | AND/OR COMPLIANCE WITH ANY FIRE CODE |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | PROVIDE AN APPLICABLE NOTE |
| | |
| | |
| | |
| | |
| | 2) SHEET A 121 - IN THEACT& GWB SCHEDULE THERE ARE |
| | INDICATION OF SPECIFICATION REFERRING TO SHEET A 700. |
| | THERE IS NO SHEET A 700 AS PART OF THIS SUBMITTAL. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACUES. |
| | |
| | 38.3.3 INTERIOR FINISH. |
| | 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH SECTION 10.2. |
| | 38.3.3.2 INTERIOR WALL AND CEILING FINISH. |
| | 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL |
| | COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B |
| | IN EXITS AND IN EXIT ACCESS CORRIDORS. |
| | 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE |
| | CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE |
| | SPECIFIED IN 38.3.3.2.1. |
| | |
| | PLEASE PROVIDE THA APPLICABLE MAUNFACTURERS SPEC SHEETS |
| | OF SHEET A 700 WITH THE APPLICABLE INFORMATION SHOWING |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET E 0.1 & 2.1 - THERE ARE INDICATIONS OF FIRE |
| | ALARM EQUIPMENT. ALL WORK ON THE FIRE ALARM SYSTEM OR |
| | ON ANY EQUIPMENT SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |