Plan Review Notes
Plan Review Notes For Permit 17070904
Permit Number 17070904
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-26 17:10:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 002 - THERE ARE NO INDICATIONS OF REVIEW
 AND/OR COMPLIANCE WITH ANY FIRE CODE
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PROVIDE AN APPLICABLE NOTE
  
  
  
  
 2) SHEET A 121 - IN THEACT& GWB SCHEDULE THERE ARE
 INDICATION OF SPECIFICATION REFERRING TO SHEET A 700.
 THERE IS NO SHEET A 700 AS PART OF THIS SUBMITTAL.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACUES.
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B
 IN EXITS AND IN EXIT ACCESS CORRIDORS.
 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE
 SPECIFIED IN 38.3.3.2.1.
  
 PLEASE PROVIDE THA APPLICABLE MAUNFACTURERS SPEC SHEETS
 OF SHEET A 700 WITH THE APPLICABLE INFORMATION SHOWING
 COMPLIANCE.
  
  
  
 3) SHEET E 0.1 & 2.1 - THERE ARE INDICATIONS OF FIRE
 ALARM EQUIPMENT. ALL WORK ON THE FIRE ALARM SYSTEM OR
 ON ANY EQUIPMENT SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPICABLE NOTE OF COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL