| 2017-08-08 13:17:02 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM STATES THAT WIRES IN THE RISER ARE |
| | SIZED BY FPL, WHICH IS INCORRECT. SIZE WIRE PER NEC AND |
| | STATE ON PLAN. NEC 215.2, 220, 310.15: FBC RE3602.1 |
| | 2. # 1 WIRE FROM METER TO DISCONNECT AND FROM |
| | DISCONNECT TO INTERIOR PANEL IS NOT SIZED PROPERLY FOR |
| | 200 AMP SERVICE . PROVIDE CORRECTION. NEC 215.2, |
| | 310.15; FBC RE3602.1 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 4. NOTE #1 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 5. NOTE 13 STATES THAT LIGHTING IN CLOSETS MUST COMPLY |
| | WITH NEC 410.8. WHICH IS NOT THE CORRECT CODE SECTION |
| | FOR LIGHTING IN CLOSETS. PROVIDE CORECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 7. CIRCUITS 13 AND 21 SHOULD BE AFCI PROTECTED BASED ON |
| | DESCRIPTION. PROVIDE CORRECITON. NEC 210.12; FBC |
| | RE3902.12 |
| | 8. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| | GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC |
| | 210.70(A)(2)(B), FBC RE3903.3 |
| | 9. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |