Plan Review Notes
Plan Review Notes For Permit 17070895
Permit Number 17070895
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-16 09:26:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - SPECIFY THE WIND DESIGN DATA ON THE
 PLANS. ( I.E. WIND SPEED AND EXPOSURE CATEGORY )
  
 2) FBC-R310.1 THE NEW SINGLE HUNG WINDOWS FOR THE
 BEDROOMS 1 AND 2 DO NOT MEET THE REQUIREMENTS OF FBC
 R310 FOR EMERGENCY AND RESCUE OPENINGS. INDICATE THE
 EXISTING WINDOW'S TYPE AND THE NET CLEAR OPENING SIZE
 OF IT. PROVIDE CALCULATIONS TO SHOW THAT THE NET CLEAR
 OPENING DIMENSIONS OF THE EXISTING WINDOW ARE NOT BEING
 REDUCED BY MORE THAN 5-PERCENT PER FBC EXISTING
 BUILDING SECTION 704.1.
  
 3) SPECIFY THE SIZE OF THE THRU BOLTS THAT ARE SHOWN ON
 TRELLIS DETAIL 6 ON SHEET A4.0. FBC-R 301.1
  
 4) TREATED ROD DOWELS SET IN EPOXY ARE SPECIFIED ON
 TRELLIS DETAIL 6 ON SHEET A4.0 TO ANCHOR THE JOISTS.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE RODS AND
 THE EPOXY THAT IS PROPOSED. PROVIDE PRODUCT APPROVALS
 OR CALCULATIONS FOR THIS CONNECTION. FBC 107.2.1.3
  
 5) ON SHEET S1.0, ACI 318 IS REFERENCED WITH VARIOUS
 EDITIONS. CHAPTER 46 OF THE 2014 FBC-R REFERENCES THE
 2011 EDITION OF ACI. PLEASE REVISE TO ACI 318-11. FBC
 107.2.1
  
 6) THE DOOR SCHEDULE ON SHEET A6.0 SPECIFIES PRODUCT
 APPROVAL FL15210.1 AND PART OF PRODUCT APPROVAL FL 4940
 WAS SUBMITTED. THE INSTALLATION INSTRUCTION PORTION OF
 THE PRODUCT APPROVAL IS REQUIRED TO BE SUBMITTED. THE
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD PER FBC 107.3.4.1.
  
 7) THE DOOR SCHEDULE ON SHEET A6.0 SPECIFIES PRODUCT
 APPROVAL NOA NO. 17-0130.01 FOR AN EXTERIOR GLAZED
 DOOR. NO PRODUCT APPROVALS WERE SUBMITTED FOR THIS
 DOOR. SUBMIT PRODUCT APPROVALS FOR THIS DOOR THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
 FLORIDA STATUTE 553.842 (5)
  
 8) THE WINDOW SCHEDULE ON SHEET A6.0 LISTS THE TYPE AS
 DOUBLE HUNG AND THE COMMENTS SPECIFY SINGLE HUNG.
 PLEASE CLARIFY. FBC 107.2.1
  
 9) NOA NO. 15-0519.08 WHICH IS LISTED IN THE WINDOW
 SCHEDULE HAS BEEN SUPERSEDED BY NOA NO. 16-0714.06.
 PLEASE UPDATE PLANS. THE PRODUCT APPROVALS ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 PER FBC 107.3.4.1.
  
 10) SPECIFY THE SLOPE OF THE CLAY TILE COVERED PORCH.
 FBC 107.2.1
  
 11) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CLAY ROOF TILE. FBC-R905.3.6 IF A ROOF
 TILE ADHESIVE IS TO BE USED, SUBMIT THE PRODUCT
 APPROVALS FOR IT. FBC 107.3.4.1
  
 12) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 ENHANCED FASTENING CALCULATIONS AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 5 OF NOA NO. 16-0425.02 FOR
 THE US PLY BUR.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  