2017-08-01 08:46:532ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070883
 8/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER THOMAS J. TWOMEY P.E. WHOSE TITLE BLOCK
 IS ON THE PLAN MUST PROVIDE HIS SIGNATURE AND SEAL TO
 THE PLAN SHEET IN COMPLIANCE WITH SECTION 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE 6" FLEX DUCTS ARE UNDERSIZED FOR 150 CFMS AT
 STANDARD 0.1" FRICTION LOSS.
  
 3) THE 7" & 8" TRANSFER DUCTS IN THE 2ND FLOOR BEDROOMS
 ARE UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL:
 THE TRANSFER DUCTS MUST BE 1-1/2 TIMES THE
 CROSS-SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE
 ROOM.
  
 4) INDICATE HOW AIR RETURNING TO THE 18X18" GRILL IN
 THE HALLWAY IS BEING TRANSFERED TO THE AIR HANDLER
 WHICH IS LOCATED IN THE MASTER BEDROOM- SECTION
 M1602.4.
  