| Plan Review Notes For Permit 17070883 |
| Permit Number |
17070883 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-01 08:46:53 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070883 | | | 8/1/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER THOMAS J. TWOMEY P.E. WHOSE TITLE BLOCK | | | IS ON THE PLAN MUST PROVIDE HIS SIGNATURE AND SEAL TO | | | THE PLAN SHEET IN COMPLIANCE WITH SECTION 61G15-23.002 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | 2) THE 6" FLEX DUCTS ARE UNDERSIZED FOR 150 CFMS AT | | | STANDARD 0.1" FRICTION LOSS. | | | | | | 3) THE 7" & 8" TRANSFER DUCTS IN THE 2ND FLOOR BEDROOMS | | | ARE UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL: | | | THE TRANSFER DUCTS MUST BE 1-1/2 TIMES THE | | | CROSS-SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE | | | ROOM. | | | | | | 4) INDICATE HOW AIR RETURNING TO THE 18X18" GRILL IN | | | THE HALLWAY IS BEING TRANSFERED TO THE AIR HANDLER | | | WHICH IS LOCATED IN THE MASTER BEDROOM- SECTION | | | M1602.4. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|