Plan Review Notes
Plan Review Notes For Permit 17070881
Permit Number 17070881
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-03 07:02:22E-MAIL SENT TO CONTRACTOR: 07:01 08/08/2017 ]
  
 TO WHOM IT MAY CONCERN:
  
 THE SUBMITTED TEST FOR MAXXIM SIM-90 UNDERLAYMENT DOES
 NOT FIT THE REQUIRED CRITERIA FROM THE 1ST PLAN REVIEW.
 THE SUBMITTED PRODUCT IS FOR A 8 INCH SLAB WITH DROPPED
 CEILING AND LAY-IN INSULATION WITHIN A PLENUM.
 WE DO HAVE TEST REPORTS FOR A PROFLEX PRODUCT SUPER SIM
 90, TESTED ON A 6 INCH CONCRETE SLAB FOR TILE, THAT WAS
 TESTED TO ASTM F 90 WITH A IIC RATING OF 50 AND TESTED
 TO ASTM E 492 WITH A STC RATING OF 52 AND A FLAME
 SPREAD OF 0 AND SMOKE DEVELOPMENT OF 0.
 YOUR CONTRACT DOES NOT REPRESENT THE USE OF THIS
 PRODUCT.
  
 DENIED: THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE
 BUT HAVE COMMENTS. TO VIEW COMMENTS FROM ALL
 DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]