| Date |
Text |
| 2017-08-03 07:02:22 | E-MAIL SENT TO CONTRACTOR: 07:01 08/08/2017 ] |
| | |
| | TO WHOM IT MAY CONCERN: |
| | |
| | THE SUBMITTED TEST FOR MAXXIM SIM-90 UNDERLAYMENT DOES |
| | NOT FIT THE REQUIRED CRITERIA FROM THE 1ST PLAN REVIEW. |
| | THE SUBMITTED PRODUCT IS FOR A 8 INCH SLAB WITH DROPPED |
| | CEILING AND LAY-IN INSULATION WITHIN A PLENUM. |
| | WE DO HAVE TEST REPORTS FOR A PROFLEX PRODUCT SUPER SIM |
| | 90, TESTED ON A 6 INCH CONCRETE SLAB FOR TILE, THAT WAS |
| | TESTED TO ASTM F 90 WITH A IIC RATING OF 50 AND TESTED |
| | TO ASTM E 492 WITH A STC RATING OF 52 AND A FLAME |
| | SPREAD OF 0 AND SMOKE DEVELOPMENT OF 0. |
| | YOUR CONTRACT DOES NOT REPRESENT THE USE OF THIS |
| | PRODUCT. |
| | |
| | DENIED: THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE |
| | BUT HAVE COMMENTS. TO VIEW COMMENTS FROM ALL |
| | DISCIPLINES: |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |