2017-07-25 13:15:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF EXISTING FIRE HYDRANTS
 AND/OR FDC LOCATION THAT MAY BE AFFECTED BY THE
 PROPOSED LOCATION.
  
 FIRE HYDRANTS AND FDC'S SHALL NO BE BLOCKED BY THE
 INSTALLATION AND ACCESSIBLE AT ALL TIMES.
  
 PLEASE INDICATE AND ACCOUNT FOR ACCESSIBLILTY.
  
  
  
 2) THERE ARE NO INDICATIONS OF GATES OR ACCESS POINTS.
 GATES SHALL HAVE KNOX PADLOCK PROVIDED FOR 24 HR
 EMERGENCY ACCESS.
  
 PLEASE PROVIDE.
  
  
  
 3) THE EXISTING SCHOOL HAS REQUIRED EXITS AND ACCESS TO
 PUBLIC WAYS. THERE ARE NO INDICATIONS THAT THE PUBLIC
 WAY ACCESS IS PROVIODED WITH THE PROPOSED. THE PROPOSED
 DETAIL REMOVES PUBLIC WAY ACCESS.
  
 PLEASE INDICATED HOW AND WHERE THE EXISTING EXIT PUBLIC
 WAY ACCESS IS MAINTAINED.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  