| Plan Review Notes For Permit 17070872 |
| Permit Number |
17070872 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-25 13:15:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF EXISTING FIRE HYDRANTS | | | AND/OR FDC LOCATION THAT MAY BE AFFECTED BY THE | | | PROPOSED LOCATION. | | | | | | FIRE HYDRANTS AND FDC'S SHALL NO BE BLOCKED BY THE | | | INSTALLATION AND ACCESSIBLE AT ALL TIMES. | | | | | | PLEASE INDICATE AND ACCOUNT FOR ACCESSIBLILTY. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF GATES OR ACCESS POINTS. | | | GATES SHALL HAVE KNOX PADLOCK PROVIDED FOR 24 HR | | | EMERGENCY ACCESS. | | | | | | PLEASE PROVIDE. | | | | | | | | | | | | 3) THE EXISTING SCHOOL HAS REQUIRED EXITS AND ACCESS TO | | | PUBLIC WAYS. THERE ARE NO INDICATIONS THAT THE PUBLIC | | | WAY ACCESS IS PROVIODED WITH THE PROPOSED. THE PROPOSED | | | DETAIL REMOVES PUBLIC WAY ACCESS. | | | | | | PLEASE INDICATED HOW AND WHERE THE EXISTING EXIT PUBLIC | | | WAY ACCESS IS MAINTAINED. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|