| 2017-09-29 16:39:21 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | |
| | 1- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE |
| | OVERHEAD GARAGE DOOR ON SHEET A3.2 TO CORRESPOND TO |
| | EXPOSURE "D". |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) BALCONY DECK UNDERLAYMENT. ARCHITECT TO SPECIFY |
| | BALCONY FLOOR FINISH. NOTE: NEED PRODUCT APPROVAL THAT |
| | IS DESIGNED TO BE USED WITH THE SPECIFIC DECK FINISH |
| | MATERIAL TO BE INSTALLED IN THIS HOUSE. IN ADDITION |
| | CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | REQUIRED. |
| | *****NOA 14-0529.02 IS GOOD ONLY FOR OPTIONS SHOWN ON |
| | TABLE 4 OF SAME NOA. AND FLORIDA PRODUCT APPROVAL |
| | FL17442-R1 IS NOT GOOD EITHER. |
| | B) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH |
| | ITEM #1 ABOVE. |
| | C) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT |
| | RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS |
| | FOR SMALL MISSILE IMPACT RESISTANT. |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY |
| | MULLION SIZE. |
| | E) FIXED WINDOWS AS SPECIFIED ON PLANS. |
| | F) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS. |
| | 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS. |
| | 4- ENGINEER WHO PREPARED THE RAS 117 CALCULATIONS FOR |
| | THE MAIN HOUSE TO PROVIDE CALCULATIONS WITH ORIGINAL |
| | SEAL AND SIGNATURE (NOT COPY) AS REQUIRED BY CHAPTER |
| | 471 F.S. |