| 2017-08-23 10:29:06 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEAS SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 2. PROVIDE NOT ON PLAN TO SHOW COMPLIANCE WITH FBC ACC |
| | 604.6 FLUSH CONTROLS. |
| | FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE |
| | COMPARTMENTS COMPLYING WITH 604.8.2 |
| | |
| | 3. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL |
| | 708.3.5 |
| | |
| | 4. A TRAP PRIMER IS REQUIRED ON FLOOR DRAINS AND ICE |
| | MACHINE DRAIN. PER FBC PL 1002.4 |
| | |
| | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 6. A BACKFLOW IS REQUIRED ON ICE MACHINE SUPPLY. PER |
| | FBC PL 608.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |