Plan Review Notes
Plan Review Notes For Permit 17070822
Permit Number 17070822
Review Stop M
Sequence Number 3
Notes
Date Text
2017-11-22 15:59:313RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17070822
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW COMBUSTION CALCULATIONS DO NOT APPEAR TO BE
 IN COMPLIANCE WITH ANY OF THE METHODS SPECIFIED UNDER
 SECTION 304 FBC-14 FUEL GAS. IF THE INTENT IS PROVIDE
 THE AIR MECHANICALLY, THE REQUIRED RATE IS CALCULATED
 AT 0.35 CFM PER 1,000 BTUH PER SECTION 304.9.
  
 2) THE NEW OUTSIDE AIR INLET IS NOT IN COMPLIANCE WITH
 SECTION 401.4 WHICH REQUIRES A 10' CLEARANCE TO THE
 ALLEY.
  
 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC. PLEASE PROVIDE AN
 AIR BALANCE CALCULATION UNDER THIS MAIN PERMIT WHICH
 TAKES INTO ACCOUNT THE KITCHEN EXHAUST HOOD RATE,
  
 4) ADVISORY: PLEASE SEE SECTION 508.1.1 WHICH REQUIRES
 THE TEMPERATURE DIFFERENTIAL BETWEEN THE MAKEUP AIR AND
 THE AIR IN THE CONDITIONED SPACE NOT TO EXCEED 10
 DEGREES F.
  
 5) THE ADDRESS ON THE PLANS DOES NOT MATCH THE ADRESS
 ON THE PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  