2017-11-22 10:33:153RD REVIEW.
  
 PREVIOUS PROVISO COMMENTS ARE RE-POSTED BELOW:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE DOOR TO THE DRY STORAGE ROOM OPENS INTO THE PATH
 OF EGRESS. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
 7.2.1.4.3 - DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 - DURING ITS SWING, ANY DOOR LEAF IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN
 FULLY OPEN, UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE
 MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THOUGH THE STORAGE ROOM IS NOT CONSTANTLY OCCUPIED, AN
 AUTOMATIC DOOR CLOSER SHALL BE INSTALLED TO ENSURE THIS
 DOOR REMIANS CLOSED AT ALL TIMES AND WILL NOT BLOCK THE
 PATH OF TRAVEL TO THE EXIT DOOR.
  
 PLEASE ENSURE A DOOR CLOSER IS INSTALLED.
  
  
 2) THE PROPOSED PROJECT SHALL COMPLY WITH NFPA 101,
 CHAPTER 36, (NOT CHAPTER 10)
  
  
  
 3) THE EXISTING HOOD AND SUPPRESSION SYSTEM SHALL
 COMPLY WITH NFPA 96 AND HAVE A CURRENT SERVICE TAG.
  
  
  
 PETER LEDUC
 FIRE MARSHAL