| 2017-11-28 07:42:00 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | 3RD REVIEW. ITEMS NOT ADDRESSED SATISFACTORILY LISTED |
| | BELOW WITH ADDITIONAL COMMENTS IN PARENTHESES: |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK |
| | AND VALUE. IT APPEARS THE VALUE LISTED ON THE PERMIT |
| | APPLICATION IS LOW. FBC 109.3 (HAVE NOT COMPLIED. THIS |
| | SHOULD INCLUDE VALUE OF ALL EQUIPMENT AND LABOR FOR A |
| | COMPLETE JOB.) |
| | 2. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE ON |
| | BUILDING. PER THE RISER DIAGRAM, THE SERVICE WIRE HAS A |
| | CAPACITY OF 400 AMPS. PROVIDE LOAD CALCULATION TO |
| | CONFIRM THE CAPACITY IS ADEQUATE. NEC 215.2, 220; FBC |
| | 107.2.1 (NOTE ON PLAN STATES THAT THE REVISED RISER IS |
| | THE CORRECTION TO THIS COMMENT, WHICH IS NOT ACCURATE. |
| | A LOAD CALCULATION IS REQUIRED. PROVIDE AS PREVIOUSLY |
| | REQUESTED.) |
| | 3. COMPLIED. |
| | 4. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA |
| | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 (HAVE NOT |
| | COMPLIED. PROVIDE AS PREVIOUSLY REQUESTED.) |
| | 5. COMPLIED. |
| | 6. COMPLIED. |
| | 7. COMPLIED. |
| | 8. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) (A NOTE WAS PROVIDED, |
| | HOWEVER, THE LIGHTING PLAN STILL SHOWS THE CIRCUITRY |
| | INCORRECT. PROVIDE CORRECTION ON PLAN TO MATCH NOTE.) |
| | 9. COMPLIED. |
| | 10. COMPLIED. |
| | 11. COMPLIED. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |