| 2017-11-27 18:11:21 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070822 |
| | ADD: 124 N. DIXIE HWY. |
| | CONT: PAN AMERICAN ENGINEERING |
| | TEL: 561-254-4858 |
| | E-MAIL: ??????????? PLEASE PROVIDE, WE COMMUNICATE WITH |
| | E-MAIL. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | COMMENTS FROM 2ND REVIEW NOT ADDRESSED |
| | DATE: 11/27/17 |
| | ACTION: DENIED |
| | |
| | 1-5) COMPLIED. |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 6) SUBMITTED NOA 16-0421.10 PGT SE-3550 OUTSWING DOOR & |
| | NOA 16-0505.04 PGT SS-3500 STOREFRONT SYSTEM, THE |
| | CONTRACTOR NOR THE DESIGNER OF RECORD HAS NOT |
| | IDENTIFIED ELEMENTS IN THE ASSEMBLY. |
| | IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7)SEMI ?COMPLIED SEE COMMENT ABOVE. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ***NEW COMMENT*** |
| | THE PRODUCT APPROVALS SUBMITTED INCLUDE DRAWING SHEETS |
| | WHICH DID NOT PRINT PROPERLY. FBC 107, PROVIDE A |
| | COMPLETE LEGIBLE FULL SIZE PRODUCT APPROVAL INDICATING |
| | METHOD OF INSTALLATION AS WELL AS COMPONENTS SUCH AS |
| | IMPACT BAR, ADA THRESHOLD. THE PRODUCT APPROVAL |
| | CONTAINS MANY DIFFERENT INSTALLATION OPTIONS. APPLICANT |
| | IS TO INDICATE WHICH IS PROPOSED. |
| | |
| | |
| | |
| | |