2017-07-25 10:26:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A-6 DETAIL #1 THE HEIGHT OF THE GRAB BAR SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4
  
 2. SHOW COMPLIANCE WITHE FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3. THE NEW ADA BATHROOM-DOES NOT COMPLY WITH THE
 CLEARANCE FOR THE TOILET, THE MIN OVERALL WIDTH SHOULD
 BE A MIN OF 7' TO PROVIDE CLEARANCE FOR THE LAVATORY
 AND THE TOILET. PER FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 4. SHT. A-2 SHOWS EXWH IN A DIFFERENT LOCATION THAN SHT
 P-1 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 5. ON SHT A-2 AND P-1 SHOWS EXISTING FIXTURES IN NEW
 ADA BATHROOM. PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 6. ALL FIXTURES IN KIT SHALL CONNECT THROUGH GREASE
 INTERCEPTOR PLEASE PROVIDE GREASE CALCULATIONS TO
 INCLUDE 3 COMP SINK HAND SINK FLOOR DRAIN AND MOPSINK.
 PER FBC PL 1003.3.1
  
 7. SHOW EXISTING HAND SINK IN KIT ON RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 8. LAVATORY IN BATHROOM SHALL HAVE TEMPERED WATER SHALL
 BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  