| 2017-07-25 10:26:46 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT A-6 DETAIL #1 THE HEIGHT OF THE GRAB BAR SHALL |
| | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC |
| | ACC 609.4 |
| | |
| | 2. SHOW COMPLIANCE WITHE FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 3. THE NEW ADA BATHROOM-DOES NOT COMPLY WITH THE |
| | CLEARANCE FOR THE TOILET, THE MIN OVERALL WIDTH SHOULD |
| | BE A MIN OF 7' TO PROVIDE CLEARANCE FOR THE LAVATORY |
| | AND THE TOILET. PER FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 4. SHT. A-2 SHOWS EXWH IN A DIFFERENT LOCATION THAN SHT |
| | P-1 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. ON SHT A-2 AND P-1 SHOWS EXISTING FIXTURES IN NEW |
| | ADA BATHROOM. PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. ALL FIXTURES IN KIT SHALL CONNECT THROUGH GREASE |
| | INTERCEPTOR PLEASE PROVIDE GREASE CALCULATIONS TO |
| | INCLUDE 3 COMP SINK HAND SINK FLOOR DRAIN AND MOPSINK. |
| | PER FBC PL 1003.3.1 |
| | |
| | 7. SHOW EXISTING HAND SINK IN KIT ON RISER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 8. LAVATORY IN BATHROOM SHALL HAVE TEMPERED WATER SHALL |
| | BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. PER FBC PL 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |